Ive read multiple times now that MeanWell are conservative with there ratings, but I want to make sure before I puchase.
I was planning to run each 1212 at 36v * 1350A = 48w, however a freind here mentioned thats its really pushing the driver and recommneded only 4 * 50w per 1 HLG240w.
The spec sheet shows const current region 89-179v, if all 5 1212's ran at 36v thats 180v...
Also, doesn't the drivers 6-8% efficiency range deduct some power that I can use?
What am I likely to get out of these drivers per 5 1212's if I maxed them out?
I guess one solution to allow for overage would be to purchase HLG-320-C1400A's
I was planning to run each 1212 at 36v * 1350A = 48w, however a freind here mentioned thats its really pushing the driver and recommneded only 4 * 50w per 1 HLG240w.
The spec sheet shows const current region 89-179v, if all 5 1212's ran at 36v thats 180v...
Also, doesn't the drivers 6-8% efficiency range deduct some power that I can use?
What am I likely to get out of these drivers per 5 1212's if I maxed them out?
I guess one solution to allow for overage would be to purchase HLG-320-C1400A's