how do you run them flipped when they are in 18 hours for veg?
1 room isnt built yet but when its built out in the basement it will flip flop with the 24x24. so it will be fine when im running at 12/12 but what happens when one room is in veg 18/6?
if i tried to seal room 1 now with 16x 1kw DE's (1200w on boost/.96/.9
=1275w x 16=20400+550=20950w total = 71480btu thats a 48k unit and a 24k unit. so 6480w +2800w max ac plus 20950w = 30230w total if i kept the DE's so 125a total draw @ 240v in this one room. the room is ran using a 100a sub panel. i could theoretically rewire this sub panel for 150-160 amps replace the 300' run of wire back to the main 200a panel and run the room sealed. then the problem is running 125 amps on a house that can at any time during the day pull some serious amperage by itself. Pool, spa, 7 tons of central ac, washing machine, elec dryer, oven, kids blow drying their hair, chest freezer, refrigerator, water heater, etc.