A 25kva transformer can carry 80% load. If you are running 240v you will get 10k amps so ten is max eight is recommended twelve is too many. At 120v you can run sixteen max. To get amps divide the kva/v you get amps.How many 1000 watts HPS have you had in a 25 kva transformer? the house main breaker is 150 amps.
I would like to know if it is possible to have 12 connected.
Thanks in advance.
at 12,000 W, you are at "roughly" 1/2 of the capacity of the transformer. That's 100 amps of load at 120V. That's 2/3 of your main capacity (if the 150A is 120V), leaving only 50 amps for the rest of the house. Magnetic ballasts will be more reactive than digital ballasts and have a lower power factor, causing the transformer to "see" more kVA power than you are actually consuming. The answer is "maybe" depending on the rest of the load and what the overall power factor is at the transformer.How many 1000 watts HPS have you had in a 25 kva transformer? the house main breaker is 150 amps.
I would like to know if it is possible to have 12 connected.
Thanks in advance.
How can I run more (sixteen) on 120v than (eight) on 240v? isn't it the same load?A 25kva transformer can carry 80% load. If you are running 240v you will get 10k amps so ten is max eight is recommended twelve is too many. At 120v you can run sixteen max. To get amps divide the kva/v you get amps.
There are 240v at the main breaker, the transformer is a green square box located on my neighbour backyard floor.at 12,000 W, you are at "roughly" 1/2 of the capacity of the transformer. That's 100 amps of load at 120V. That's 2/3 of your main capacity (if the 150A is 120V), leaving only 50 amps for the rest of the house. Magnetic ballasts will be more reactive than digital ballasts and have a lower power factor, causing the transformer to "see" more kVA power than you are actually consuming. The answer is "maybe" depending on the rest of the load and what the overall power factor is at the transformer.
I being thinking about to go with LED but I want something that I can install as same height (7' to 8') as a 1000 watts hps bulb, 1000w / 240v = 4.2 amps.you need to look at all the loads
at 230V youre only about 6A per light so depending on your loads youre getting up there, 12 should be fine if you dont have any other big loads like compressors, well pumps, massive AC units etc.
im guessing with 12HPS you do have massive AC units as well. if youre tight on power would be better to replace 12K of HPS with 8K of LED and cut your AC load nearly in half
sure. so use big ass cobs, 100-200W each, reasonably close together. (4) 200 W cobs will beat any HPS in yield, coverage, and penetrationI being thinking about to go with LED but I want something that I can install as same height (7' to 8') as a 1000 watts hps bulb, 1000w / 240v = 4.2 amps.
Thanks in advance.
1)Which cobs can be run 100-200 watts?sure. so use big ass cobs, 100-200W each, reasonably close together. (4) 200 W cobs will beat any HPS in yield, coverage, and penetration
because 240v is twice as many volts as 120v generating power more efficiently than 120v .240v x 15A = 3600W 120v x 15A = 1800W half as much power so twice as many needed at 120 than 240, . If you are running 120v you are not getting the benefit of the transformer in the first place. A transformer can be center tapped, for 480v, and 240v and quarter tapped for 120v. I would recommend you hire an electrician to help you size your transformer and determine the proper panel allocation.How can I run more (sixteen) on 120v than (eight) on 240v? isn't it the same load?
Thanks in advance.
That transformer is for more than your residence. That transformer is being shared. you are going to have to contact the electric company to find out how much available power is left on that transformer, unless it is private owned and installed and then you will have to ask your neighbor, otherwise you will have to install your own transformer, about $15kThere are 240v at the main breaker, the transformer is a green square box located on my neighbour backyard floor.
Thanks in advanced.