It depends on the rating and voltage of the supply.
We have a 60 amp 600v service, with a 45kva transformer stepping down to 120/208 into a 3ph 225amp panel. we are running 34 1000w lights this very moment, a 36,000 btu a/c, a 14,000 btu a/c, 4 10 inch inline fans, 2 12 inch inline fans, like 18 wall fans, pumps, 6x 4' 4 lamp t5's...fridge, cameras, security system, hallway lighting exit signs..we do pull close to 50 amps at times on the primary side, when all the lights and both a/c's are on.
70amps at 240v on the secondary side of the xformer is a lot different than a 70 amp 600v service...~16,800w vs ~42,000w and usually services are labelled based on the the primary side over current rating of the supply conductors to the building so that needs to be clarified for us.
Also more info on the rating of that main service entrance panel would help. Is the transformer on a pole outside or is there one in the building?
Regardless, if you have 3 phase 480 or 600 coming in, even if that meter is only good for 70 amp, you would be able to simply ditch the small sub panel, upgrade the main panel to a 225 amp or something in that neighborhood.
Say that meter is only rated for 70 amp, but you have a 3 phase 480 or 600v supply.
70a x 480v = 33,600 watts
70a x 600v = 42,000 watts.
Not quite that simple but it illustrates the point.
Seems to me that the service, if it is 480 or even better 600v is adequate for 15k, easily, with enough room for some a/c, fans etc. It's just that main panel will probably need to be upgraded and I'd just ditch the sub panel.