GreeneryBob
Well-Known Member
I am an electrician.Here is a picture of my 18 gauge solid copper. I find it not too rigid. Perhaps 16 or 14 gauge would be more of a problem. Personally I would minimize connections and just use solid.
Edit: I only raise/lower my lights 3 or 4 time during a grow. THe rigidity of the wire never even crossed my mind as a problem with the 18 gauge solid wire. I sure you will find different preferred ways on this subject.
What you want for the runs between lights and driver is #14 (or larger) SOOW, then drop down to #18 solid for termination to the molex connectors, that cable is rated for all kinds of abuse, high and low temps, UV, chemical spills, 600v, etc.
Go to any electrical wholesaler or building supply store and they can hook you up.
PS, ask for 3 wire as it is a flexible cord/not a cable, so a ground isn't automatically included.