You wanna know the truth? I have no idea what that homeowner did.Well, first off, looks like the dryer has 2 single pole 30a breakers instead of one double pole 30a breaker. That should be rectified. I think the same is true for the 15amps too. Looks like 2 single poles, instead of one double pole. Yikes. And the main switch should be a double pole, not a single pole. Looks like the DIY the previous owner did is Half assed. At this point, I think I (and I'm sure gohydro and others) would like to see inside the old MAIN box.
Do see differently gohydro?
The breaker in the MAIN panel feeding the sub look like 2 single poles. WTF?
The dryer breaker in the sub ALSO looks like (2) single poles. A second WTF?
I think that's a MLO panel so what that blue handled 15 is for beats me.